DIRECT REPLACEMENT UPGRADES
 
No wiring changes necessary (see Notes)
Use existing wiring base and flame scanner.
C-Series to D-Series or E110 Flame-Monitor
C-Series Model
D-Series
Flame-Monitor
25CU6-5065
70D10, 71D60
72DUV1
E110, ED510,
EP160, EUV1
25CU6-5066
70D20, 71D60
72DUV1
E110, ED510,
EP260, EUV1
25CF6-5022
70D10, 71D60
72D1R1
E110, ED510,
EP160, E1R1
25CF6-5023
70D20, 71D60
72D1R1
E110, ED510,
EP260, E1R1
25CU6-5062
70D30, 71D80
72DUV1
E110, ED510,
EP380, EUV1
25CU6-5063
70D30, 71D90
72DUV1
E110, ED510,
EP390, EUV1
25CF6-5020
70D30, 71D80
72D1R1
E110, ED510,
EP380, E1R1
25CF6-5021
70D30, 71D90
72D1R1
E110, ED510,
EP390, E1R1
25CJ5-5010
70D30, 71D80
72DRT1
E110, ED510,
EP380, ERT1
25CJ5-5011
70D30, 71D90
72DRT1
E110, ED510,
EP390, ERT1


Notes:
L1-13, 13-3 circuits: Some C-Series and D-Series controls were installed on a burner that did not have a fuel valve end switch terminal (13 – 3) and the operating control was wired between L1 and 3. When upgrading to a Flame-Monitor on these installations, after verifying a fuel valve end switch is not installed (e.g., no wire on terminal 13), jumper terminal 13 to 3.

Early Spark Termination (Terminal X):
On the non-modulating C-Series and D-Series (70D30) controls, terminal X would provide a 5 second pilot trial for ignition (PTFI). If terminal X is required, terminal 5 must be jumpered to terminal 10 when using the EP380, EP381, or EP390 programmers.

 
CAUTION
Refer to Bulletin E-1101 for proper installation, grounding, operational and safety checkout procedures. Perform safety checks of the entire system prior to allowing fuel entry to boiler.

 
D-Series Chassis and
Programmer
E-Series
Programmer
All Flame-Monitor controls
require an E110 chassis
and ED510 display module.
70D10 and 71D60
EP160
70D10 and 71D61
EP161
70D10 and 71D70
EP170
70D20 and 71D60
EP260
70D20 and 71D61
EP261
70D20 and 71D70
EP270
70D30 and 71D80
EP380
70D30 and 71D81
EP381
70D30 and 71D90
EP390
D-Series Amplifier
E-Series Amplifier
Use With Flame Scanners
72DUV1
EUV1
UV1A, UV2, UV8A, UV90, 45UV3-1050
72D1R1
E1R1
48PT2
72DRT1
ERT1*
45CM1,69ND1
72DUVS4
EUVS4
45UV5-1007, -1008, -1009


*Ensure S2 is connected to earth ground when using ERT1.