EPD Programmer Modules
The EPD programmers offer a cost effective version of the Flame-Monitor control. EPD style programmers provide the same start-up programming, safe start check, and flame monitoring supervision as their counterpart EP style programmers. The major difference between EP and EPD style programmers is that the EPD programmers incorporate a built-in display consisting of seven (7) LED indicator lights to annunciate the current operating status of the Flame-Monitor control, as well as the reason of the last lockout condition. EPD programmers provide a switch-selectable option that requires the air flow switch (terminals 3-P) to be open at the start of the operating cycle. The EPD programmers include an RJ45 style connector to interface with a remote alpha-numeric display (P/N ED510) 1 and two (2) RJ style connectors to connect to an E500 communication interface.
The EPD programmers do not require the ED510 alpha-numeric display to operate. The ED510 display is optional for EPD programmers, but is required for the EP-style programmers.
The EPD Flame-Monitor System can be upgraded to include an E300 Expansion Module (remote ED510 alpha-numeric display required). A set of test jacks located on the front of the programmer module provide a 0-10 VDC output to indicate flame signal strength.

 
Part Number
Description
EPD160 30 Sec. Purge, 10 & 15 Sec. TFI, Non-Recycle Modulation
EPD161 30 Sec. Purge, 10 & 30 Sec. TFI, Non-Recycle, Modulation
EPD170 30 Sec. Purge, 5 & 10 Sec. TFI, Early Spark Termination, Non-Recycle, Modulation
EPD260 30 Sec. Purge, 10 & 15 Sec. TFI, Recycle, Modulation
EPD261 30 Sec. Purge, 10 & 30 Sec. TFI, Recycle, Modulation
EPD270 30 Sec. Purge, 5 & 10 Sec. TFI, Early Spark Termination, Recycle, Modulation
EPD380 30 Sec. Purge, 5 & 10 Sec. TFI, Recycle, No Modulation
EPD381 15 Sec. Purge, 5 & 10 Sec. TFI, Recycle, No Modulation
EPD382 0 Sec. Purge, 5 & 10 Sec. TFI, Recycle, No Modulation
EPD390 90 Sec. Purge, 5 & 10 Sec. TFI, Recycle, No Modulation

 
GENERAL COMMENTS
EPD100 and EPD200 series programmers provide an additional 30 second low-fire purge.
All programmers offer selectable Prove Air Flow (3-P circuit) Open To Start feature
All programmers have 4 second FFRT.
EPD Style Programmers include a built-in LED display.

 
CAUTION: While programmers are mechanically interchangeable in that they mate with a common wiring base, you should select the correct model for your application. Inappropriate application of a control could result in an unsafe condition hazardous to life and property. Selection of a control for a particular application should be made by a competent professional, such as a boiler/burner service technician licensed by a state or other government agency


1. The EPD programmers must have an Engineering code of 02 or higher to interface with an ED510 display

We Carry:

(Click Name for more info)

 

 

 

Most Items available for immediate shipment!


-Copyright 2005 M&M Controls, All Rights Reserved

ALL REGISTERED TRADEMARKS ARE FULLY ACKNOWLEDGED BY:
M&M Control Service, Inc.

(ALL NAMES UNINTENTIONALLY EXCLUDED FROM THIS LIST WILL BE INCLUDED IN THE NEXT REVISION UPON OUR NOTIFICATION)
*This list may vary, as names not appearing on this list are entitled to the acknowledgment of their Trademarks by M&M Control Service, Inc.

(Powers, also known as, POWERS REGULATOR, MCC POWERS, POWERS-FIAT, POWERS PROCESS CONTROLS, CRANE POWERS and POWERS, a Watts Industries Company.  The POWERS trademark is owned by Powers, A Division of Watts Water Technologies, Inc.  M&M Control Service, Inc. Is a Stocking Distributor for Powers)

M&M CONTROL SERVICE, INC. DOES NOT REPRESENT OR CLAIM ANY AFFILIATION WITH ANY MANUFACTURER. WE FULLY ACKNOWLEDGE ALL TRADEMARKS AND/OR NAMES WHICH ARE PICTURED AND/OR LISTED THROUGHOUT THE M&M CONTROL SERVICE, INC. WEBSITE.